Serviceline
Serviceline Industriële Sensoren
Serviceline Explosiebeveiliging

Niet beschikbaar voor verkoop

This product has been replaced.Go to replacement product KFD2-SR2-Ex2.W
Niet beschikbaar voor verkoop

Isolated Switch Amplifier KFD2-SR2-Ex2.W

KFD2-SR2-Ex2.W
  • 2-channel
  • Control circuit EEx ia IIC
  • Reversible mode of operation
  • 1 signal output with 1 changeover contact per channel
  • EMC acc. to NAMUR NE 21

De complete datasheet als PDF downloaden:


Technische gegevens KFD2-SR2-Ex2.W

Productbeschrijving
24 V DC:
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage20 ... 30 V DC
Ripple≤ 10 %
Rated current≤ 50 mA
Power dissipation0.7 W
Power consumption< 1.3 W
Input
Connectionterminals 1+, 3-; 4+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Pulse/Pause ratiomin. 20 ms / min. 20 ms
Line fault detectionbreakage I ≤ 0.1 mA
Output
Connectionoutput I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Output I, IIsignal ; relay
Contact loading253 V AC/2 A /cos φ > 0.7; 40 V DC/2 A resistive load;
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Mechanical life107 switching cycles
Transfer characteristics
Switching frequency≤ 10 Hz
Directive conformity
Electromagnetic compatibilityStandards
Directive 89/336/EECacc. to EN 50081-2 / EN 50082-2
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 150 g
Data for application in connection with hazardous areas
EC-Type Examination CertificatePTB 00 ATEX 2080 ; for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2]
Directive conformityStandards
Directive 94/9/ECEN 50014, EN 50020

Documents: KFD2-SR2-Ex2.W

ManualsTaalBestandstypeBestandsgrootte
Manual Isolated Barriers K-systemENGPDF760 KB
Manuel pour Barrières Isolées de Système KFRAPDF759 KB
Handbuch Trennbarrieren K-SystemGERPDF745 KB
Manual Isolated Barriers K-systemRUSPDF4107 KB

Approvals+Certificates: KFD2-SR2-Ex2.W

CertificatesCertificaatnummerBestandstypeBestandsgrootte
Europe PTB ATEX Category (1) GDPTB 00 ATEX 2080PDF2272 KB
USA FMFM Listed (Approval Guide)LINK---
Download het compendium voor Functionele Veiligheid

Gratis downloadbestand: Compendium voor Functionele Veiligheid

Download ons gratis compendium voor Functionele Veiligheid in pdf-vorm en leer meer over de specifieke normen en methodes voor risicobeperking. We tonen je ook hoe je veiligheidsapparatuur in je systeem kan integreren en bieden je een handige woordenlijst om je te helpen bij je dagelijkse taken.