Serviceline Industriële Sensoren
Serviceline Explosiebeveiliging

Niet beschikbaar voor verkoop

This product has been replaced.Go to replacement product KFD2-SR2-Ex2.W
Niet beschikbaar voor verkoop
Niet beschikbaar voor verkoop

Isolated Switch Amplifier KFD2-SR2-Ex2.W

KFD2-SR2-Ex2.W
  • 2-channel
  • Control circuit EEx ia IIC
  • Reversible mode of operation
  • 1 signal output with 1 changeover contact per channel
  • EMC acc. to NAMUR NE 21

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  KFD2-SR2-Ex2.W

Productbeschrijving
24 V DC:
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage20 ... 30 V DC
Ripple≤ 10 %
Rated current≤ 50 mA
Power dissipation0.7 W
Power consumption< 1.3 W
Input
Connectionterminals 1+, 3-; 4+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Pulse/Pause ratiomin. 20 ms / min. 20 ms
Line fault detectionbreakage I ≤ 0.1 mA
Output
Connectionoutput I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Output I, IIsignal ; relay
Contact loading253 V AC/2 A /cos φ > 0.7; 40 V DC/2 A resistive load;
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Mechanical life107 switching cycles
Transfer characteristics
Switching frequency≤ 10 Hz
Directive conformity
Electromagnetic compatibilityStandards
Directive 89/336/EECacc. to EN 50081-2 / EN 50082-2
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 150 g
Data for application in connection with hazardous areas
EC-Type Examination CertificatePTB 00 ATEX 2080 ; for additional certificates see www.pepperl-fuchs.com
Group, category, type of protectionEx-Hexagon II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2]
Directive conformityStandards
Directive 94/9/ECEN 50014, EN 50020

Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFD2-SR2-Ex2.W

Product Documentation: KFD2-SR2-Ex2.W

Taalkeuze:
ManualsTaalBestandstypeBestandsgrootte
ManualENGPDF3685 KB
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.