Serviceline Industriële Sensoren
Serviceline Explosiebeveiliging
Niet beschikbaar voor verkoop
Niet beschikbaar voor verkoop

Universal PROFIBUS Power Hub, Gateway Motherboard MB-FB-GTR

MB-FB-GTR
  • For 2 PROFIBUS gateway modules
  • Redundant configuration
  • Part of Segment Coupler 3

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  MB-FB-GTR

General specifications
Design / MountingMotherboard based
Supply
Rated voltage19.2 ... 35 V SELV/PELV
Rated current2 ... 3 A
Indicators/operating means
Fault signalVFC alarm output via connectors
DIP switchaddress 0 ... 61
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Galvanic isolationIEC 62103
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Pollution degreemax. 2, according to IEC 60664
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Housing materialPolycarbonate
Degree of protectionIP20
Massapprox. 300 g
Dimensions
Height220 mm
Width95 mm
Depth65 mm
MountingDIN mounting rail
Coatingconformal coated
Data for application in connection with hazardous areas
CertificateTÜV 04 ATEX 2500 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approvalCoC 3024816, CoC 3024816C
Approved forClass I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, AEx/Ex nA IIC T4
IECEx approvalIECEx TUN 13.0038X
Approved forEx nA IIC T4 Gc
Certificates and approvals
Marine approvalDNV A-14038
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242603
ECLASS 12.027242603
ECLASS 11.027242603
ECLASS 10.0.127242603
ECLASS 9.027242603
ECLASS 8.027242603
ECLASS 5.127242603
ETIM 9.0EC001598
ETIM 8.0EC001598
ETIM 7.0EC001598
ETIM 6.0EC001598
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: MB-FB-GTR

Product Documentation: MB-FB-GTR

Taalkeuze:
ManualsTaalBestandstypeBestandsgrootte
Manual for use with HD2-FB*, MB-FB*.GEN, MBHD-FB*.GEN, MBHD-FB-D-4R.GEN, MB-FB-GT, MB-FB-GTRENGPDF2401 KB

Design / Simulation: MB-FB-GTR

Taalkeuze:
CADTaalBestandstypeBestandsgrootte
DXF Drawings Power Hub MB-FB-*, Subject to change without notice / DXF Zeichnungen Power Hub MB-FB-*, Änderungen vorbehaltenALLZIP8539 KB

Approvals: MB-FB-GTR

Taalkeuze:
CertificatesCertificaatnummerTaalBestandstypeBestandsgrootte
Canada FMFM 19 CA 0011XALLPDF356 KB
DNV MarineTAA0000272ALLPDF100 KB
Europe TUV Nord ATEX Category 3 GTÜV 04 ATEX 2500XALLPDF1498 KB
India PESO (India) CCOEA/P/HQ/KA/104/5874 (P507650)ALLPDF101 KB
USA FMFM 19 US 0015XALLPDF213 KB
Worldwide TUV Nord Ex nA nC IECEx nAIECEx TUN 13.0038XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2267BALLPDF1039 KB

Aanverwante producten: MB-FB-GTR

Matching System Components

PROFIBUS DP V1 / For 4 segments PA, Couples PROFIBUS PA devices transparently to PROFIBUS DP, Optional redundant configuration, Installation in Zone 2/Class I, Div. 2, Up to 12 Mbit/s, auto adapting, IECEx approval, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunkpa