Serviceline Industriële Sensoren
Serviceline Explosiebeveiliging
Niet beschikbaar voor verkoop
Niet beschikbaar voor verkoop

DART High-Density Power Hub, Generic Interface KT-MB-FB-D-4R.GEN

KT-MB-FB-D-4R.GEN
  • 4 segments, load-sharing redundancy
  • Output: 22 ... 24 V/360 mA, Ex ib IIC
  • DART for intrinsically safe, high-power segments
  • Redundant connection to PROFIBUS DP
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Customizable for any host system
  • Individual modules per segment
  • Optimized for size and quality, low heat dissipation
  • Passive impedance for high reliability
  • Installation in Zone 2

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  KT-MB-FB-D-4R.GEN

General specifications
Design / MountingMotherboard based
Supply
Connectionredundant
Rated voltage19.2 ... 35 V SELV/PELV
Rated current3230 ... 1820 mA
Fieldbus connection
Number of segments
Redundant4
Rated voltage20.8 ... 22.3 V
Rated current360 ... 10 mA
Short-circuit current413 mA
Host-side25-pin Sub-D socket
Host-rated voltage10.1 ... 11 V
Host-rated current... 40 mA
Host short-circuit current... 50 mA
Terminating resistor100 Ω , integrated
Indicators/operating means
LED ERRred flashing: short-circuit or undervoltage at output
LED PWRgreen if Uout > 21 V
Fault signalVFC alarm output via connectors
Rated voltage50 V
Rated current1 A
Galvanic isolation
Host-side/Supply50 V functional insulation acc. to IEC 62103
Fieldbus segment/Host-side250 V safe galvanic isolation acc. to EN 60079-11:2007
Fieldbus segment/Fieldbus segment60 V safe galvanic isolation acc. to EN 60079-11:2007
Fieldbus segment/Supply250 V safe galvanic isolation acc. to EN 60079-11:2007
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Standard conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F) when mounted on a horizontal DIN rail
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g , 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Pollution degreemax. 2, according to IEC 60664
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typeplug with screw flange
Core cross section2.5 mm2
Housing materialPolycarbonate
Degree of protectionIP20
Massapprox. 2.4 kg
Dimensionssee dimensions
MountingDIN mounting rail , according to DIN EN 60715
Data for application in connection with hazardous areas
EU-type examination certificatePTB 10 ATEX 2034 , PTB 10 ATEX 2020 X , PTB 11 ATEX 2010 X
MarkingEx-Hexagon II 2 G Ex ib IIC T4 , Ex-Hexagon II (2) D [Ex ib] IIIC , Ex-Hexagon II 3(2) G Ex nAc [ib] IIC T4
Supply
Maximum safe voltage35 V
Host interface
Maximum safe voltage35 V
Alarm output
Maximum safe voltage35 V
Directive conformity
Directive 94/9/ECEN 60079-0:2009 , EN 60079-11:2007 , EN 60079-15:2006 , EN 60079-25:2010 , EN 61241-11:2006
International approvals
IECEx approvalIECEx PTB 12.0022X IECEx PTB 12.0023X IECEx PTB 12.0024X
Approved for[Ex ib] IIC
[Ex ib] IIIC
Ex nAc II T4
Certificates and approvals
FOUNDATION FieldbusFF-831
Marine approvalDNV A-14038
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242610
ETIM 9.0EC001600
ETIM 8.0EC001600
ETIM 7.0EC001600
ETIM 6.0EC001600
ETIM 5.0EC001604
UNSPSC 12.139121004

Details: KT-MB-FB-D-4R.GEN

Informative Literature: KT-MB-FB-D-4R.GEN

Taalkeuze:
LiteratureTaalBestandstypeBestandsgrootte
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: KT-MB-FB-D-4R.GEN

Taalkeuze:
ManualsTaalBestandstypeBestandsgrootte
ManualENGPDF4188 KB

Design / Simulation: KT-MB-FB-D-4R.GEN

Taalkeuze:
CADTaalBestandstypeBestandsgrootte
CAD 2-D / CAD 2-DALLZIP2933 KB

Approvals: KT-MB-FB-D-4R.GEN

Taalkeuze:
CertificatesCertificaatnummerTaalBestandstypeBestandsgrootte
DNV MarineTAA0000272ALLPDF100 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0813ALLPDF1171 KB

Aanverwante producten: KT-MB-FB-D-4R.GEN

Matching System Components

Comprehensive diagnostics for fieldbus physical layer and power supply, Plug-in Module for the FieldConnex Power Hub, Precise measurements through passive circuits, For commissioning, online monitoring and troubleshooting, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunkpa

Basic monitoring for power supply output and health, Plug-in Module for the FieldConnex Power Hub, Plug and play - no engineering required, For online monitoring, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunkpa
Diagnostics for fieldbus physical layer and power supply, Plug-in Module for the FieldConnex Power Hub, Plug and play - no engineering required, For online monitoring, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunkpa
For 2 gateway modules, For PROFIBUS PA, Redundant configuration, Installation in Zone 2/Class I, Div. 2, Spring terminals or screw terminals selectable, IECEx approval, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunk, Device coupler location [3]: Zone 1 - high-power trunkpa