Serviceline Industriële Sensoren
Serviceline Explosiebeveiliging

Niet beschikbaar voor verkoop

This product has been replaced.Go to replacement product KFD0-CS-1.50
Niet beschikbaar voor verkoop
Niet beschikbaar voor verkoop

Repeater KFD0-CS-1.50

KFD0-CS-1.50
  • 1-channel signal conditioner
  • 24 V DC supply (loop powered)
  • Current input/output 4 mA ... 20 mA
  • transmitter power supply
  • Accuracy 0.1 %
  • Reverse polarity protection
  • Up to SIL 2 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  KFD0-CS-1.50

General specifications
Signal typeAnalog input/analog output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Rated voltageloop powered
Power dissipation0.2 W
Control circuit
Connectionterminals 12-, 11+
Voltage10 ... 35 V DC
Current4 ... 20 mA
Power dissipation< 150 mW per channel at 25 mA and U < 26.1 V
< 400 mW per channel at 25 mA und U > 26.1 V
Field circuit
Connectionterminals 1+, 2-
Voltage≥ 0.9 x Uin - (0.23 x current in mA) - 0.7 for 10 V < Uin < 26.1 V
≥ 23 V - (0.23 x current in mA) for Uin > 26.1 V
Short-circuit currentmax. 100 mA
Transfer currentmax. 25 mA
Transfer characteristics
Accuracy0.1 %
Deviation
After calibrationUin ≥ 5 V ± 20 µA/Uin ≤ 5 V ± 50 µA incl. calibration, linearity, hysteresis and output load fluctuations at the field side; at 20 °C (68 °F)
Influence of ambient temperature≤ ± 2 µA/K at Uin ≤ 20 V; ≤ ± 5 µA/K at Uin > 20 V
Rise time≤ 5 ms at 4 ... 20 mA and Uin = input voltage < 26 V
Galvanic isolation
Input/Outputbasic insulation according to IEC 62103, rated insulation voltage 300 Veff
Indicators/settings
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Insulation coordinationEN 50178:1997
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1
Height107 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210120
ECLASS 12.027210120
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 9.0EC002653
ETIM 8.0EC002653
ETIM 7.0EC002653
ETIM 6.0EC002653
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFD0-CS-1.50

Product Documentation: KFD0-CS-1.50

Taalkeuze:
Safety and Security DocumentationTaalBestandstypeBestandsgrootte
HandleidingHOLPDF56 KB
Functional Safety ManualENGPDF1969 KB
Manuals
System ManualENGPDF3694 KB

Design / Simulation: KFD0-CS-1.50

Taalkeuze:
CADTaalBestandstypeBestandsgrootte
CAD 3-D / CAD 3-DALLSTP105 KB
CAD Portal / CAD PortalALLLINK---
CAE
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ44 KB

Approvals: KFD0-CS-1.50

Taalkeuze:
CertificatesCertificaatnummerTaalBestandstypeBestandsgrootte
exida Functional Safety AssessmentP+F 03/07-04-R013ALLPDF284 KB

Aanverwante producten: KFD0-CS-1.50

Matching System Components
Cable trunking is integrated in the mounting profile, Safe spacious separation of field and control signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector