| | Products Process Automation |
|  | |  | | | | | | | |
| |  |
|  | | | | | |  | |  |  | | Datasheet as PDF in following languages: |
|  | |  | |  |  | | General specifications |  | |
|  | | Supply |  |  |  | | Connection | via Termination Board |
|
|  |  | | Rated voltage | 20.4 ... 30 V via Termination Board |
|
| |  |  | | Rated current | 140 mA at 24 V and 20 mA |
|
|  |  | | Power loss | ≤ 1.8 W at 20 mA |
|
|  |  | | Power consumption | ≤ 3.3 W at 20 mA |
|
|
|
|  | | Hazardous area connection |  |  |  | | Connection | terminals 1+, 4-; 2+, 5-; 3+, 6-; 7+, 8- |
|
|  |  | | Input signal | 4 ... 20 mA , limited to approx. 30 mA |
|
|  |  | | Available voltage | ≥ 15 V at 20 mA |
|
| | |
|
|  | | Safe area connection |  |  |  | | Connection | terminals 11+, 14-; 12+, 15-; 13+, 16-; 17+, 18- |
|
| |  |  | | Voltage drop | approx. 6 V or internal resistance 300 Ω at 20 mA |
|
|  |  | | Output signal | 4 ... 20 mA or 1 ... 5 V (on 250 Ω, 0.1 % internal shunt) 4 ... 20 mA (sink mode), operating voltage 15 ... 26 V |
|
|  |  | | Output load | 0 ... 300 Ω (source mode) |
|
| |
|
|  | | Transfer characteristics |  |  |  | | Deviation | at 20 °C (293 K) ≤ ± 0.1 % incl. non-linearity and hysteresis (source mode 4 ... 20 mA) ≤ ± 0.2 % incl. non-linearity and hysteresis (sink mode 4 ... 20 mA) ≤ ± 0.2 % incl. non-linearity and hysteresis (source mode 1 ... 5 V) ≤ ± 0.2 % incl. non-linearity and hysteresis (analog output mode 4 ... 20 mA) |
|
|  |  | | Frequency range | hazardous area into the safe area: bandwidth with 0.5 Vss 0 ... 3 kHz (-3 dB) safe area into the hazardous area: bandwidth with 0.5 Vss 0 ... 3 kHz (-3 dB) |
|
|  |  | | Rise time | 10 to 90 % ≤ 20 ms |
|
|
|
|  | | Indicators/settings |  | |  |  | | DIP-switch | selection of operating mode: current source, current sink or voltage source |
|
|  |  | | Factory setting | analog input with source output |
|
|  |  | | Labeling | space for labeling at the front |
|
|
|
|  | | Directive conformity |  |  |  | | Electromagnetic compatibility |  |  |  |  | | Directive 2004/108/EC | EN 61326-1:2006 |
|
|
|
|
|
|
|
|  | | Conformity |  |  |  | | Electromagnetic compatibility | NE 21 |
|
|  |  | | Protection degree | IEC 60529 |
|
|
|
|  | | Ambient conditions |  |  |  | | Ambient temperature | -20 ... 60 °C |
|
|
|
|  | | Mechanical specifications |  | | | |  |  | | Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 in) |
|
|
|
|  | | Data for application in conjunction with hazardous areas |  |  |  | | EC-Type Examination Certificate | CESI 02 ATEX 086 , for additional certificates see www.pepperl-fuchs.com |  |  |  | | Group, category, type of protection | II (1)GD [Ex ia] IIC, [Ex iaD] [circuit(s) in zone 0/1/2/20/21/22] |
|
|
|
|
|
|  |  | | Statement of conformity | Pepperl+Fuchs |  |  |  | | Group, category, type of protection, temperature classification | II 3G Ex nA II T4 X |
|
|
|
|
|
|  |  | | Directive conformity |  |  |  |  | | Directive 94/9/EC | EN 60079-0, EN 60079-11, EN 61241-11, EN 61241-0, EN 60079-15 , EN 60079-26 |
|
|
|
|
|
|
|
|
|
|
|
|  |
|  | |
|  | | |
| |
|  | Informatie+Service Telefoon +31 (0)73-750 71 07 Fax +31 (0)73-644 47 49 |
|